Effects of radiant cooling and heating system on thermal comfort and productivity in elderly care facilities

Masato Kimura, Toshiharu Ikaga, Yoshihisa Hirayama

研究成果: Conference contribution

1 被引用数 (Scopus)

抄録

Field measurements were conducted in a nursing home located in the hot and humid city of Kumamoto, Japan, between July and September 2010. In addition, a questionnaire survey was conducted with care staff during the measurement procedure to evaluate the effect of the thermal environment on thermal comfort and productivity. Results indicated that radiant cooling and heating system provided a stable temperature. Furthermore, the system coefficient of performance was calculated to evaluate the performance of the radiant cooling system and was 1.8-3.1. As a result of the questionnaire survey, about half of the staff were satisfied with the current thermal environment in the facility, reporting that it was comfortable and did not reduce working efficiency.

本文言語English
ホスト出版物のタイトル12th International Conference on Indoor Air Quality and Climate 2011
ページ1809-1814
ページ数6
出版ステータスPublished - 2011 12月 1
イベント12th International Conference on Indoor Air Quality and Climate 2011 - Austin, TX, United States
継続期間: 2011 6月 52011 6月 10

出版物シリーズ

名前12th International Conference on Indoor Air Quality and Climate 2011
3

Other

Other12th International Conference on Indoor Air Quality and Climate 2011
国/地域United States
CityAustin, TX
Period11/6/511/6/10