Proposal of an eco-friendly high-performance air-conditioning system. Part 1. Possibility of improving existing air-conditioning system by an evapo-transpiration condenser

Huynh Thi Minh Thu, Haruki Sato

研究成果: Article査読

12 被引用数 (Scopus)

抄録

Air-conditioning (AC) system consumes high energy and releases waste-heat. In the present study, we propose a method to improve its performance and minimize waste-heat by replacing existing air-cooled condenser by an evaporation and transpiration, evapo-transpiration, condenser. The improvement is confirmed by performing experiment for a conventional air-cooled AC system and a water-cooled AC system. Condenser temperature in the air-cooled system is higher than outdoor-temperature by 5-10 C, while it is -5 to 5 C in case of the testing system. From simulation results, saving energy consumption is expected to reach up to 30% in summer with the testing system. Based on these results, an evapo-transpiration heat-exchanger was developed as a new condenser. Heat-transfer coefficient of the testing heat-exchanger is at least 4 times higher than that of air-cooled condenser. Even hot fluid is used inside copper-tubing, its outlet-air temperature is as nearly as outdoor temperature.

本文言語English
ページ(範囲)1589-1595
ページ数7
ジャーナルInternational Journal of Refrigeration
36
6
DOI
出版ステータスPublished - 2013 9

ASJC Scopus subject areas

  • 建築および建設
  • 機械工学

フィンガープリント

「Proposal of an eco-friendly high-performance air-conditioning system. Part 1. Possibility of improving existing air-conditioning system by an evapo-transpiration condenser」の研究トピックを掘り下げます。これらがまとまってユニークなフィンガープリントを構成します。